The SVTG series excitation systems (SVGG, SVGD, SVG, SVSK) (hereinafter the ES) are static, silicon-controlled, high-speed excitation systems.
General characteristics of ES Series
- covered range of generator rated power:
– up to 1000 MW; - types of generator excitation:
– brush;
– brushless; - range of rated excitation current and voltage:
– excitation current: up to 7500 A;
– excitation voltage: up to 700 V; - excitation transformer types:
– oil- or dry-immersed transformer;
– indoor or outdoor transformer;
– one-group or two-group transformer; - power supply circuits:
– one-group and two-group;
– shunt-wound and separate excitation; - Automated Excitation controllers:
– automatic (3 types) + system stabilizer (PSS);
– manual; - Automated Excitation Control redundancy circuits:
– redundancy according to 1+1 circuit: dual-channel full redundancy;
– no redundancy – single channel with automated and manual controllers; - power converters redundancy circuits:
– standby according to 1+1 circuit: dual-channel full redundancy of converters;
– redundancy according to N-1 circuit: single-channel redundancy via one redundant converter;
– no redundancy; - number of parallel thyristors on the converter arm:
– 1;
– 3 or 4; - number of parallel converters in one ES channel:
– 1;
– 2 or more; - power converter cooling:
– natural air cooling;
– forced air cooling;
– combined air cooling; - excitation switching to standby station excitation system:
– with excitation switching devices to the standby ES;
– without excitation switching devices to the standby ES;
– with digital “field-protective relay” (FPR); - completeness:
– full completeness – without using former ES elements;
– partial completeness – using former ES elements:
– power transformer (one-group and two-group);
– field suppression discharging resistance;
– field suppression device (FSD);
– devices for connection to standby station excitation system; - logging tools:
– recorder embedded into the Automatic Excitation Controller;
– stand-alone recorder (not included into Automatic Excitation Controller) for independent control over the Automatic Excitation Controller run;
– event log file built into the AEC4 controller. - instruments for ES control, monitoring and diagnostics:
– operator touch pad;
– Computer workstation (a human-machine interface); - network interfaces for communication with Automated process control systems:
– Profibus DP, Modbus RTU, Modbus TCP (Ethernet), CAN, etc.
Basic technical specifications
ES functions:
- automatic excitation and suppression during generator start and shutdown;
- initial excitation from the field flashing unit and from the generator residual voltage;
- automatic adjustment of generator voltage to line voltage;
- soft start with initial excitation;
- cutting into mains by precision synchronization method in normal modes of the power system:
– from the unit control desk/main control desk synchronizer;
– from automatic excitation controller (AEC):
* adjustment of generator voltage to the network voltage;
* turbine frequency adjustment;
* generator switch closing with control of level and difference in phases of generator and network voltages;
*out-of-phase reclosing independent relay; - cutting in the network by the self-synchronization method in emergency modes of the power system;
- excitation switching to a standby station excitation system according to standard rules without changing the generator operation mode;
- rating of the generator short-circuit and no-load (when power is supplied from an external source for self-excitation system);
- adjustable parameters in Automated Excitation Control:
– generator voltage (main mode);
– generator reactive power;
– cos (?) generator. - control structure Automatic Excitation Control – “ARV-SD (stabilizing)”;
- back-up manual controller of excitation current:
– switching to a manual controller in case of automatic controller feedback malfunction;
– switching to a manual controller with maintaining excitation setpoint;
– excitation control through “More/Less” commands; - rotor electromechanical oscillations damping, securing stability of the generator and the power system;
- droop (compounding) and voltage drop compensation in unit transformer for generator full and reactive current;
- excitation boost;
- electric braking mode;
- line charging mode;
- re-synchronization mode upon loss of field;
- excitation winding temperature calculation;
- generator active and reactive energy accounting;
- password-protected change of settings.
The ES parameters control accuracy:
- generator voltage – 0.2%;
- generator reactive power – 0.5%;
- cos (?) generator – 0.5%;
- excitation current in the manual mode – 0.5%.
The ES parameter control range (adjustable):
- generator voltage:
– no load mode – from 5% to 110%;
– network mode – from 95% to 110%. - excitation current manual control:
– no load mode – from 5% to 110% of the generator rated no-load current;
– network mode – from the minimum limit of 20 … 40% to 110% of the rated generator current.
Control system
All CS tasks are fulfilled by a software and hardware approach.
The control structure of the Automatic Excitation Control – “ARV-SDPK” with the following control channels (see figure down):
- PID voltage controller:
– by voltage deviation – dUs (proportional-integral section);
– by the generator voltage derivative – Us’ (differential section); - PSS – power system stabilizer:
– by the excitation current derivative – If`;
– by the generator frequency derivative – Fs`;
– by the generator frequency deviation – dFs. - DF – direct feedback on rotor voltage for brushless excitation systems;
Note: the control structure for generators of up to 60 MW can be switched from the “Power System Stabilizer” mode to the PID-controller mode.
Additional functions of Automatic Excitation Control for Generator/motor at Pumped Storage Power Plants:
- supported starting circuits:
– direct-on-line and inductor start;
– auxiliary motor start;
– start with a soft starter; - start with a frequency converter and excitation current control over the “4-20mA” channel from frequency converter.
Structural design of ARV-SDPK control system
Automatic excitation control limiters:
- minimum and maximum generator voltage;
- minimum and maximum excitation current;
- maximum no-load excitation current with power off and generator overfrequency;
- minimum excitation – limitation of generator reactive power subject to active power («Q=f(P)»);
- generator overvoltage during its frequency drop («V/Hz=const»);
- stator overload limiter by time-dependent characteristic;
- rotor overload limiter by time-dependent characteristic;
- forcing time by rotor overvoltage characteristic;
Protection system
Protection types for operation on thyristor excitation system:
- generator overvoltage;
- generator overcurrent;
- loss of excitation;
- internal short circuits in thyristor converters;
- short circuits in excitation circuit;
- overvoltage in arrester excitation circuit;
- loss of conduction on the converter arm;
- loss of conduction in parallel thyristors on arms;
- no signal from voltage transformer during field flashing;
- no signal from voltage transformer and current transformer for the generator in operation mode with switching to manual mode maintaining the excitation setpoint;
- against forcing excessive duration limiter failure and excitation overcurrent limiter failure;
- against the “P/Q” minimum excitation limiter failure and transfer to a manual mode with set excitation that ensures over-excitation mode;
- excitation circuits insulation resistance decrease protection:
– built-in insulation control device with resistance indication on the console terminal, operator touch-panel, AWS;
– protection unit “BENDER” with resistance display panel on the UPS cabinet door or on AWS (optional); - against resistance increase of excitation circuit “cable-brush rig-rotor”;
- design excitation winding temperature protection;
- protection against the stator circuit breaker a-contacts malfunction through redundancy on the stator current;
- overcurrent and overtemperature protection of power rectifier transformer:
– basic current protection – ensured independently from ES by using a block incorporate into the generator protection panel;
– basic temperature protection – secured independently from the ES by using tinternal protection block built into the transformer;
– backup current and temperature protection – provided by the ES built-in protection;
Protection for operation on the backup station ES:
- protection against excitation circuits insulation resistance decrease;
- protection unit “Rotor Protection Relay (RPR)”:
– protection types:
• against forcing excessive duration and excitation overcurrent;
• for short circuits in the excitation circuit;
– the RPR block consists of:
• RPR controller;
• Warning (If> 1.05 * Inom) relay – combined signal of overload starting point and RPR non-readiness.
• De-excitation relay – a signal informing about the request to decrease the excitation upon overload time expiration;
• Shutdown relay – a signal to shut down if excitation overcurrent fails to decrease upon overcurrent time expiration or upon the short-circuit current.
Note: The RPR unit serves as the basic protection for operation on the backup excitation system and as the backup protection for operation on the thyristor excitation system.